草成人在线观看,玖玖玖亚洲精品,2008高清一道国产,av免费在线观看网站不卡顿

Language
News
News

With years of experience in designing and assembling complete sets of generator sets

Reasons for abnormal shutdown of diesel generator sets during normal operation

Time:2023-11-04

During the operation of the diesel generator set, if the operator did not stop the operation, the diesel generator set automatically stopped rotating. There are many reasons for this type of malfunction, some of which are sudden drops to idle speed at rated speed and then automatic shutdown; Some have a gradual decrease in speed until the machine stops; Some diesel generator sets operate at rated speed, and the speed suddenly fluctuates, then automatically shuts down; There is also the sound of parts colliding with each other during the automatic shutdown process. In summary, the scope of the above-mentioned faults generally includes three aspects: fuel supply system, valve distribution system, and various moving components of diesel generator set.

Cause of malfunction:

1. The diesel fuel in the fuel tank is labeled incorrectly.

2. The fixing screws of the fuel injection pump drive plate of the diesel generator set are loose.

3. The fuel injection pump does not spray oil.

4. The return screws of the fuel supply system are loose.

5. The fuel pump does not supply oil.

6. Each oil inlet filter of the diesel generator set is blocked.

Troubleshooting method:

If this diesel generator set malfunctions in winter, the first consideration should be the impact of ambient temperature on the diesel generator set.

2. Check the return screw of the fuel supply system and tighten it.

3. Check the fixing screws of the transmission plate of the fuel injection pump governor assembly for any abnormalities.

4. Continuously press the oil delivery pump and then start the diesel generator set. It was found that the diesel generator set stopped almost 1 minute after being started. After repeating twice, it was found that there was insufficient oil in the low-pressure oil circuit of the diesel generator set.

5. Check the inlet filter screen of the oil transfer pump and find that the filter screen is blocked by broken ice. After cleaning and assembly, open the vent screw of the fuel injection pump and press the fuel transfer pump to vent. After exhaust, tighten the exhaust screw and restart the diesel generator set. It was found that the diesel generator set was running smoothly without any shutdown phenomenon, and the fault was eliminated.

Guangzhou Saiwei Energy Technology Co., Ltd. is a comprehensive enterprise specializing in design, production, and generator installation. Guangzhou Saiwei has many years of experience in engineering design and installation services. For many years, Guangzhou Saiwei has been committed to providing every customer with comprehensive products and energy solutions, including technical consulting, whole machine and generator supply, operation training, etc., with leading technology and first-class quality. The product range covers land diesel generator sets, marine generator sets, high-voltage generator sets, etc., and is widely used in industries such as power, communication, iron towers, healthcare, financial systems, data centers, etc. Welcome to inquire: 13302262088